🔥 Sauna heater: smart switch in a plug-in box
Goal: keep Russell's heater plug as it is, get a daily schedule in the app, and never touch the building's breaker box.
Read first. The heater is 2000 W, about 16.7 amps. A 20 amp switch is the minimum, and 16.7 A is a bit over the usual 80% rule (16 A) for non-stop loads. The wall outlet must be a 20 amp one (it has a T-shaped slot) and should power only the heater. If it is a plain 15 amp outlet, do not run the heater on it. Mains wiring can start fires or shock: have an electrician or handy friend build the box and check it. Open Sesame has not verified the parts fit together.
1. How it connects
Power path: wall outlet → cord with plug → switch inside box → outlet on box → heater plug. Black goes through the switch. White and green go straight to the outlet; the switch's neutral terminal also joins the white wire so its WiFi part has power. Use a cord grip where the cord enters the box.
2. Step by step
- Unplug everything. Cut the outlet end off the 12-gauge 20 A extension cord. The plug end is the input cord.
- Feed it through the cord grip into the box and tighten the grip.
- Black from the cord → switch LINE IN. A short black wire from switch LOAD → outlet brass screw.
- White from the cord → outlet silver screw, and a second short white to the switch N terminal (wire nut).
- Green from the cord → outlet green screw.
- Close the box and cover it. Plug it in, pair the switch in its app, and set a daily schedule.
- Set the heater's own knob to ON and the temperature wanted. Test once that it comes back on after the switch cuts power and restores it.
3. What to buy on Amazon
Smart switch (about $29.99): SURAIELEC 20A WiFi Timer Switch. Checked 25 Nov: in stock, 120V, 20A, 1HP. The listing does not state a heater (resistive) rating. 16.7 A is under 20 A but above the 16 A continuous mark, so ask SURAIELEC support or pick a 30 A relay if unsure.
Box: checked 25 Nov: the Suplevel and Toptozl boxes both say "Currently unavailable" and are sealed GFCI outlet boxes, not a good home for the switch. Search instead for a plain weatherproof junction box (deep, NEMA 3R) and a separate 5-20R 20 amp outlet plus a weatherproof outlet cover.
Input cord: 12-gauge 20 amp extension cord
The heater: AYCHLG 110V 2KW (already owned)
4. Check the outlet first
Look at the wall outlet. A 20 A outlet has one slot with a sideways T. Two plain straight slots means 15 A: ask the landlord before running a 2000 W heater there.